Heating with Humidification (Heater Load, Water or Steam Needed, Equipment Check)

To bring cold, dry air to the temperature and humidity you need, how much heat must the heater supply and how much water or steam must the humidifier add, and are the heater and humidifier big enough?

Steady-flow balance for heating air and adding moisture: the moisture the humidifier must add, the energy that steam or spray water brings in, the heater load that remains, and both checked against the heater and humidifier capacities.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Total (barometric) pressurekPaBarometric pressure at the site: 101.325 kPa at sea level.
Air volume flow enteringm³/sVolume flow of air entering the unit at the entering temperature.
Air entering
Entering dry-bulb temperature°CDry-bulb temperature of the air entering, usually winter outdoor or mixed air.
Entering relative humidity%Relative humidity of the air entering.
Air leaving
Leaving dry-bulb temperature°CDry-bulb temperature the leaving air must have.
Leaving relative humidity%Relative humidity the leaving air must have.
Humidifier and capacities
Humidifier typechoiceSteam injection adds moisture and heat; spray or pad humidification adds liquid water that cools the air as it evaporates.
Enthalpy of the steam or water addedkJ/kgEnthalpy of the steam or water added: about 2,675 kJ/kg for steam near atmospheric pressure (steam table), or 4.18 × water temperature for liquid water.
Heater capacitykWRated output of the heater or heating coil at these conditions.
Humidifier capacitykg/hRated output of the humidifier in kilograms of water per hour.

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Total (barometric) pressure
Illustration: Total (barometric) pressureA pressure gauge whose needle moves with Total (barometric) pressure; the needle follows the value you type.PExample: 101.325 kPaTotal (barometric) pressure
What it is
The total pressure of the moist air, the barometric pressure at the site, used in the humidity ratios and specific volume.
Units and format
Enter a number in kPa: kilopascals. The form accepts 50 kPa to 110 kPa. Required: the tool does not calculate until every input is valid.
Example
The form opens with 101.325 kPa as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Changes the humidity ratios and the dry-air mass flow slightly.
Get it right
Use about 101.325 kPa at sea level and the local value at altitude.
What this means: Air volume flow entering
Illustration: Air volume flow enteringA pipe with liquid or gas moving through it; Air volume flow entering is the volume that passes per unit of time.V̇₁Example: 1 m³/sAir volume flow entering
What it is
The volume of air entering the unit each second at the entering condition, which gives the dry-air mass flow.
Units and format
Enter a number in m³/s: m³/s. The form accepts 0.001 m³/s to 1000 m³/s. Required: the tool does not calculate until every input is valid.
Example
The form opens with 1 m³/s as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The heater load and water added rise in proportion.
Get it right
Use the flow at the entering temperature; flows quoted at standard conditions differ.

Air entering

What this means: Entering dry-bulb temperature
Illustration: Entering dry-bulb temperatureA thermometer whose level rises with Entering dry-bulb temperature; the level follows the value you type.T₁Example: 5 °CEntering dry-bulb temperature
What it is
The dry-bulb temperature of the air entering the heater, usually winter outdoor air or mixed air.
Units and format
Enter a number in °C: degrees Celsius. The form accepts 0 °C to 50 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 5 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Colder entering air raises the heater load.
Get it right
Use the coldest condition the system must meet; the tool accepts 0 to 50 °C.
What this means: Entering relative humidity
Illustration: Entering relative humidityA bar of 100 parts with the share marked; Entering relative humidity is that share out of 100. The bar follows the value you type.0 %100 %φ₁Example: 40%Entering relative humidity
What it is
The relative humidity of the air entering the unit, which with its temperature sets the moisture it already carries.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0.1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 40% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Drier entering air needs more water added.
Get it right
Cold air at high relative humidity still carries little moisture.

Air leaving

What this means: Leaving dry-bulb temperature
Illustration: Leaving dry-bulb temperatureA thermometer whose level rises with Leaving dry-bulb temperature; the level follows the value you type.T₃Example: 22 °CLeaving dry-bulb temperature
What it is
The dry-bulb temperature the conditioned air must have when it leaves the unit.
Units and format
Enter a number in °C: degrees Celsius. The form accepts 0 °C to 60 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 22 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher leaving temperature raises the heater load.
Get it right
It must be above the entering temperature for this process.
What this means: Leaving relative humidity
Illustration: Leaving relative humidityA bar of 100 parts with the share marked; Leaving relative humidity is that share out of 100. The bar follows the value you type.0 %100 %φ₃Example: 45%Leaving relative humidity
What it is
The relative humidity the conditioned air must have when it leaves the unit.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0.1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 45% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher target raises the water added and, with spray, the heater load.
Get it right
The leaving air must hold at least as much moisture as the entering air.

Humidifier and capacities

What this means: Humidifier type
Illustration: Humidifier typeThe options for Humidifier type, with the one currently selected highlighted.Steam injectionWater spray or evaporative pad (adiabatic)Example: Steam injectionHumidifier type
What it is
How moisture is added: steam injection brings latent heat with it, while spray or pad humidification adds liquid water that takes its latent heat from the air.
Units and format
Choose one of 2 options from the list: Steam injection; Water spray or evaporative pad (adiabatic).
Example
The form opens with “Steam injection” selected as a worked example. Choose the option that matches your case.
Effect on the result
Changes only the plausibility check; the enthalpy you enter sets the heater load.
Get it right
Match it to the enthalpy below: about 2,675 kJ/kg for steam, under 500 kJ/kg for water.
What this means: Enthalpy of the steam or water added
Illustration: Enthalpy of the steam or water addedA store filling up with energy; Enthalpy of the steam or water added is the total amount of work or heat involved.h_wExample: 2675 kJ/kgEnthalpy of the steam or water added
What it is
The specific enthalpy of the steam or water entering the airstream from the humidifier, which is the energy it brings in per kilogram added.
Units and format
Enter a number in kJ/kg: kJ/kg. The form accepts 0 kJ/kg to 3500 kJ/kg. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2675 kJ/kg as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher enthalpy lowers the heater load needed.
Get it right
For liquid water use about 4.18 × its temperature in °C; for steam read the steam table at its pressure.
What this means: Heater capacity
Illustration: Heater capacityA motor driving a shaft; Heater capacity is the rate at which it does work, energy per second.Q_capExample: 25 kWHeater capacity
What it is
The heat output the heater or heating coil can deliver at these air conditions.
Units and format
Enter a number in kW: kilowatts. The form accepts 0 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 25 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Only moves the pass or fail line of the heater check.
Get it right
Coil ratings depend on water or steam supply temperature; use the selection at your conditions.
What this means: Humidifier capacity
Illustration: Humidifier capacityItems moving past a point on a conveyor; Humidifier capacity is how many pass in each unit of time.count pointM_capExample: 30 kg/hHumidifier capacity
What it is
The mass of water or steam per hour the humidifier can deliver into the air at full output.
Units and format
Enter a number in kg/h: kg/h. The form accepts 0 kg/h to 100000 kg/h. Required: the tool does not calculate until every input is valid.
Example
The form opens with 30 kg/h as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Only moves the pass or fail line of the humidifier check.
Get it right
Steam humidifier ratings are in kilograms of steam per hour; check the rating at your supply pressure.

Method and formulas

  1. Each state: p_v = φ p_sat(T) (Hyland–Wexler), ω = 0.622 p_v ÷ (P − p_v), h = 1.005 T + ω (2,500.9 + 1.82 T); dry-air mass flow ṁ_a = V̇₁ ÷ v₁.
  2. Water added ṁ_w = ṁ_a (ω₃ − ω₁).
  3. Heater load Q = ṁ_a (h₃ − h₁) − ṁ_w h_w; when the steam brings more heat than needed, the heater load is zero.
  4. Example: 1 m³/s of air from 5 °C and 40 % to 22 °C and 45 % needs 23.87 kg/h of steam at 2,675 kJ/kg and a 20.81 kW heater; a 25 kW heater and 30 kg/h humidifier meet it.

Limitations

  • All added water is assumed absorbed; spray humidifiers that leave droplets or wet the duct deliver less, and their water treatment matters.
  • Air temperatures from 0 to 60 °C; relative humidity is taken over liquid water.
  • Steady design point only; controls, duct losses and fan heat are not included.
  • Example values are illustrations. Replace them with values for your actual system.

Typical uses

  • Size the heater and humidifier for a cleanroom, laboratory, museum or printing room
  • Check winter humidification for static control or comfort
  • Compare steam injection with spray humidification for the same duty

Who it is for

  • Mechanical services designers
  • HVAC technicians
  • Facility engineers

What you get

  • Heater load
  • Water or steam added and the energy it brings
  • Humidity ratio, enthalpy and dew point in and out
  • Heater and humidifier capacity checks

Interpreting the result

  • Spray humidification needs more heater capacity than steam for the same leaving state, because the water takes its latent heat from the air.
  • Cold outdoor air holds little moisture, so even modest indoor humidity targets need a lot of added water in winter.

Before relying on the result

  • Check the humidifier maker’s absorption distance in the duct before placing coils, filters or bends downstream.

References

  • Çengel Y. A. and Boles M. A., Thermodynamics: An Engineering Approach, 5th edition (McGraw-Hill, 2006), chapter 14 (section 14-7: heating with humidification). Method reference; no tables, figures or examples are reproduced.
  • ASHRAE Handbook—Fundamentals (SI), chapter 1 Psychrometrics: Hyland–Wexler saturation pressure.

Learn the Concepts Behind This Tool

These KEVOS® Library readings explain the method this tool uses, with worked examples.

KEVOS® tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.

Open the Heating with Humidification (Heater Load, Water or Steam Needed, Equipment Check) calculator