Heat Pump and Chiller COP Check (Carnot Limit, Second-Law Efficiency, Running Cost)

Is the COP claimed or measured for this heat pump or chiller possible at these temperatures, how close is it to the Carnot limit, and what does it cost to run?

Check of a heat pump or chiller’s coefficient of performance against the second law: evaporating and condensing temperatures from the source and sink temperatures and the approach temperatures you enter, the Carnot (reversible) COP for heating or cooling, the actual COP from the duty and electrical input, the second-law efficiency, the yearly electricity cost, and the input power at your minimum efficiency, against the Carnot limit and the minimum efficiency you accept.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
DutychoiceWhether the useful output is heat delivered (heat pump) or heat removed (chiller).
Source (cold-side) temperature°CTemperature of the cold side: outdoor air or ground for a heat pump, chilled water or the cold room for a chiller.
Sink (hot-side) temperature°CTemperature of the hot side: heating water for a heat pump, condenser air or cooling water for a chiller.
Evaporator approach (source minus evaporating)KHow far the evaporating refrigerant runs below the source (from the unit’s design data).
Condenser approach (condensing minus sink)KHow far the condensing refrigerant runs above the sink.
Performance and cost
Duty (heating or cooling output)kWRated or measured heating or cooling output at these temperatures.
Electrical inputkWRated or measured electrical input at the same condition.
Lowest second-law efficiency accepted%Lowest share of the Carnot COP you accept as realistic for this kind of unit (your own benchmark).
Electricity price (incl. GST)AUD/kWhElectricity price including GST, or ex GST for a GST-registered business.
Running hours per yearh/yearRunning hours at this duty per year.

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Duty
Illustration: DutyThe options for Duty, with the one currently selected highlighted.Heating (heat delivered to the sink)Cooling (heat taken from the source)Example: Heating (heat delivered t…Duty
What it is
Whether the useful output is the heat delivered on the hot side, as for a heat pump, or the heat taken from the cold side, as for a chiller.
Units and format
Choose one of 2 options from the list: Heating (heat delivered to the sink); Cooling (heat taken from the source).
Example
The form opens with “Heating (heat delivered to the sink)” selected as a worked example. Choose the option that matches your case.
Effect on the result
Switches between the heating and cooling Carnot COP.
Get it right
A heat pump’s Carnot COP is always one more than a chiller’s at the same temperatures; choose the duty you are rating.
What this means: Source (cold-side) temperature
Illustration: Source (cold-side) temperatureA thermometer whose level rises with Source (cold-side) temperature; the level follows the value you type.T_sExample: 7 °CSource (cold-side) temperature
What it is
The temperature of the cold side the machine draws heat from: outdoor air or ground for a heat pump, the chilled water or cold room for a chiller.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 200 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 7 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A warmer source reduces the temperature lift and raises the Carnot COP.
Get it right
Use the temperature at the rated condition you are checking, not an annual average.
What this means: Sink (hot-side) temperature
Illustration: Sink (hot-side) temperatureA thermometer whose level rises with Sink (hot-side) temperature; the level follows the value you type.T_kExample: 45 °CSink (hot-side) temperature
What it is
The temperature of the hot side the machine rejects heat into: the heating water for a heat pump, or the condenser air or cooling water for a chiller.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 300 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 45 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A hotter sink increases the lift and lowers the Carnot COP.
Get it right
For heating water use the flow temperature leaving the heat pump.
What this means: Evaporator approach (source minus evaporating)
Illustration: Evaporator approach (source minus evaporating)A thermometer whose level rises with Evaporator approach (source minus evaporating); the level follows the value you type.TExample: 5 KEvaporator approach (source minus evaporating)
What it is
How many degrees the evaporating refrigerant runs below the source temperature, the approach the evaporator needs to take in heat.
Units and format
Enter a number in K: kelvin (a difference of 1 K equals 1 °C). The form accepts 0 K to 50 K. Required: the tool does not calculate until every input is valid.
Example
The form opens with 5 K as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A larger approach lowers the evaporating temperature and the Carnot COP.
Get it right
Take it from the unit’s design data; a fouled or iced evaporator increases it.
What this means: Condenser approach (condensing minus sink)
Illustration: Condenser approach (condensing minus sink)A thermometer whose level rises with Condenser approach (condensing minus sink); the level follows the value you type.TExample: 5 KCondenser approach (condensing minus sink)
What it is
How many degrees the condensing refrigerant runs above the sink temperature, the approach the condenser needs to reject heat.
Units and format
Enter a number in K: kelvin (a difference of 1 K equals 1 °C). The form accepts 0 K to 50 K. Required: the tool does not calculate until every input is valid.
Example
The form opens with 5 K as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A larger approach raises the condensing temperature and lowers the Carnot COP.
Get it right
Take it from the unit’s design data; a dirty condenser coil increases it.

Performance and cost

What this means: Duty (heating or cooling output)
Illustration: Duty (heating or cooling output)A motor driving a shaft; Duty (heating or cooling output) is the rate at which it does work, energy per second.QExample: 50 kWDuty (heating or cooling output)
What it is
The heating or cooling output of the machine at the stated temperatures, rated or measured.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 50 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The actual COP and second-law efficiency rise in proportion.
Get it right
Use output and input from the same test condition; mixing a rated output with a measured input gives a meaningless COP.
What this means: Electrical input
Illustration: Electrical inputA motor driving a shaft; Electrical input is the rate at which it does work, energy per second.PExample: 15 kWElectrical input
What it is
The electrical power drawn by the machine at the same condition as the output, including the compressor and any fans or pumps the rating includes.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 15 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher input lowers the COP and raises the running cost.
Get it right
Include the same auxiliaries the rating includes; leaving out fans flatters the COP.
What this means: Lowest second-law efficiency accepted
Illustration: Lowest second-law efficiency acceptedA bar of 100 parts with the share marked; Lowest second-law efficiency accepted is that share out of 100. The bar follows the value you type.0 %100 %Example: 40%Lowest second-law efficiency accepted
What it is
The lowest share of the Carnot COP you accept as realistic for this type of machine, your benchmark for judging the claim.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 40% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Only moves the pass or fail line and the input power at that efficiency.
Get it right
Set it from your own experience or independent test data; this tool does not give a value.
What this means: Electricity price (incl. GST)
Illustration: Electricity price (incl. GST)A stack of coins and a note representing the money amount Electricity price (incl. GST).$Example: 0.3 AUD/kWhElectricity price (incl. GST)
What it is
The cost of one kilowatt-hour of electricity to the site, used for the yearly running cost.
Units and format
Enter a number in AUD/kWh: Australian dollars per kilowatt-hour. The form accepts 0 AUD/kWh to 100 AUD/kWh. Required: the tool does not calculate until every input is valid.
Example
The form opens with 0.3 AUD/kWh as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The yearly running cost rises in proportion.
Get it right
State whether it includes GST; a GST-registered business normally works ex GST.
What this means: Running hours per year
Illustration: Running hours per yearA timeline from a start mark to an end mark; Running hours per year is the time between them.startendtExample: 2000 h/yearRunning hours per year
What it is
The number of hours a year the machine runs at this duty, used for the yearly running cost.
Units and format
Enter a number in h/year: h/year. The form accepts 0 h/year to 8784 h/year. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2000 h/year as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The yearly running cost rises in proportion.
Get it right
Use equivalent full-load hours; part-load running at lower input counts for less.

Method and formulas

  1. Evaporating T_e = source − evaporator approach; condensing T_c = sink + condenser approach (kelvin).
  2. Carnot COP: heating T_c ÷ (T_c − T_e), cooling T_e ÷ (T_c − T_e), the reversed Carnot cycle (Fermi eqs 58–60).
  3. Actual COP = duty ÷ input; second-law efficiency = actual ÷ Carnot; yearly cost = input × hours × price; input at the minimum efficiency = duty ÷ (minimum × Carnot COP).
  4. Example: Carnot COP 6.7323, actual 3.3333, a second-law efficiency of 49.513 % and A$9,000 a year.

Limitations

  • Uses the refrigerant’s evaporating and condensing temperatures from your approach values; a unit tested to a standard rating condition must be compared at that condition.
  • Steady-state duty only: defrost, part-load cycling, pumps and fans outside the measured input are not included.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Test a supplier’s COP claim before buying a heat pump or chiller
  • Check a measured COP after commissioning
  • Show how lowering the sink temperature cuts running cost

Who it is for

  • Mechanical and building services engineers
  • Energy managers
  • Plant engineers

What you get

  • Evaporating and condensing temperatures
  • Carnot COP and actual COP
  • Second-law efficiency
  • Yearly running cost and input power at your minimum efficiency

Interpreting the result

  • The Carnot COP depends on the temperature lift, so a heat pump delivering 35 °C water rather than 55 °C can use markedly less power for the same heat.

References

  • Fermi E., Thermodynamics (Dover Publications, 1956; first published by Prentice-Hall, 1937), pp. 31–45. Method reference; no text, examples or tables are reproduced.

Learn the Concepts Behind This Tool

These KEVOS® Library readings explain the method this tool uses, with worked examples.

KEVOS® tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.

Open the Heat Pump and Chiller COP Check (Carnot Limit, Second-Law Efficiency, Running Cost) calculator