Heat Engine and Heat Pump Second-Law Check (Carnot Limit, Entropy Generated, Lost Work)

Is the efficiency or COP claimed for this engine, chiller or heat pump possible between its two temperatures, how close is it to the Carnot limit, and how much work does its irreversibility cost?

Second-law check of a heat engine, refrigerator or chiller, or heat pump working between a hot and a cold temperature: the actual efficiency or coefficient of performance from the heat and work rates, the Carnot limit from the absolute temperatures, the share of that limit achieved, the heat at the other reservoir from the energy balance, the entropy generated from the Clausius inequality and the lost work against an ideal reversible machine, against a credible share of the Carnot limit you set.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
MachinechoiceWhat the machine does: turn heat into work (engine), remove heat from a cold space (refrigerator or chiller) or deliver heat to a warm space (heat pump).
Heat rate: taken in (engine), cooling (chiller) or heating delivered (heat pump)kWThe useful heat rate: heat taken in by an engine, cooling capacity of a chiller, or heating capacity of a heat pump, at the same operating point as the power.
Work or power: delivered (engine) or taken in (chiller, heat pump)kWShaft work delivered by an engine, or electrical or shaft power taken in by a chiller or heat pump, at the same operating point.
Hot reservoir temperature°CTemperature of the hot side the machine exchanges heat with (the heat sink for a chiller or heat pump, the heat source for an engine).
Cold reservoir temperature°CTemperature of the cold side (the cooled space or fluid for a chiller, the outdoor air, ground or water for a heat pump, the sink for an engine).
Largest credible share of the Carnot limit%The highest share of the Carnot limit you would accept without measured evidence, from your own test data or experience of comparable machines; no value is built in.

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Machine
Illustration: MachineThe options for Machine, with the one currently selected highlighted.Heat engine (heat in, work out)Refrigerator or chiller (cooling, work in)Heat pump (heating, work in)Example: Heat pump (heating, work…Machine
What it is
The kind of machine being checked: an engine turns heat into work, a refrigerator or chiller pumps heat out of a cold space, and a heat pump delivers heat into a warm space. It sets which Carnot limit applies.
Units and format
Choose one of 3 options from the list: Heat engine (heat in, work out); Refrigerator or chiller (cooling, work in); Heat pump (heating, work in).
Example
The form opens with “Heat pump (heating, work in)” selected as a worked example. Choose the option that matches your case.
Effect on the result
Changes the Carnot limit formula and the meaning of the heat rate and power fields.
Get it right
A reverse-cycle air conditioner is a refrigerator when cooling and a heat pump when heating; check each mode with its own figures.
What this means: Heat rate: taken in (engine), cooling (chiller)…
Illustration: Heat rate: taken in (engine), cooling (chiller) or heating delivered (heat pump)Heat flowing from a hot side to a cold side through a wall or into a material; Heat rate: taken in (engine), cooling (chiller) or heating delivered (heat pump) sets how much heat moves or is stored.hotcoldQExample: 10 kWHeat rate: taken in (engine), cooling (chille…
What it is
The useful heat flow of the machine at one operating point: the heat an engine takes in, the cooling a chiller provides, or the heating a heat pump delivers.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 10 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
For a chiller or heat pump the COP, and its share of the Carnot limit, rise in proportion to it.
Get it right
Take the heat rate and the power from the same test point; mixing a rated capacity with a different power reading gives a false COP.
What this means: Work or power: delivered (engine) or taken in (…
Illustration: Work or power: delivered (engine) or taken in (chiller, heat pump)A motor driving a shaft; Work or power: delivered (engine) or taken in (chiller, heat pump) is the rate at which it does work, energy per second.WExample: 2.5 kWWork or power: delivered (engine) or taken in…
What it is
The work flow of the machine at the same operating point: shaft work an engine delivers, or the electrical or shaft power a chiller or heat pump takes in.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2.5 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A larger power input lowers the COP of a chiller or heat pump; a larger output raises an engine’s efficiency.
Get it right
Include the compressor, fans and pumps that the claimed COP includes, and no more; ratings usually state which loads are counted.
What this means: Hot reservoir temperature
Illustration: Hot reservoir temperatureA thermometer whose level rises with Hot reservoir temperature; the level follows the value you type.ThExample: 45 °CHot reservoir temperature
What it is
The temperature of the hot side the machine exchanges heat with: the heat source of an engine, or the space, water or air a chiller or heat pump rejects heat to or heats.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -200 °C to 2000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 45 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A hotter hot side raises an engine’s Carnot limit but lowers the Carnot COP of a chiller or heat pump.
Get it right
Use the temperature of the fluid at the heat exchanger, not a room set point; a heat pump heating water to 55 °C works against 55 °C or more.
What this means: Cold reservoir temperature
Illustration: Cold reservoir temperatureA thermometer whose level rises with Cold reservoir temperature; the level follows the value you type.TcExample: 5 °CCold reservoir temperature
What it is
The temperature of the cold side: the sink of an engine, the chilled space or water of a refrigerator, or the outdoor air, ground or water a heat pump draws heat from.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -270 °C to 2000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 5 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Moving it closer to the hot side raises the Carnot COP and lowers an engine’s Carnot efficiency.
Get it right
It must be lower than the hot side; for a heat pump on a cold night use that night’s outdoor temperature, not an annual average.
What this means: Largest credible share of the Carnot limit
Illustration: Largest credible share of the Carnot limitA bar of 100 parts with the share marked; Largest credible share of the Carnot limit is that share out of 100. The bar follows the value you type.0 %100 %Example: 60%Largest credible share of the Carnot limit
What it is
The highest share of the Carnot limit you are prepared to accept for this kind of machine without seeing test evidence, used to flag claims that are possible in principle but unusually good.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 60% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Only moves the line between a credible claim and one close to the limit; the calculated values do not change.
Get it right
Base it on measured data for comparable machines at similar temperatures; a single figure for all machine types is rarely right.

Method and formulas

  1. Absolute temperatures T = t + 273.15. Carnot limits: engine 1 − Tc ÷ Th; refrigerator Tc ÷ (Th − Tc); heat pump Th ÷ (Th − Tc).
  2. Energy balance for the heat at the other reservoir; entropy generated by the Clausius inequality, S_gen = Σ Q_out ÷ T − Σ Q_in ÷ T, which must not be negative.
  3. Lost work = the difference between the actual work and the work of a reversible machine with the same heat duty; it equals T × S_gen, with T the cold reservoir for an engine or heat pump and the hot reservoir for a refrigerator.
  4. Example: a heat pump giving 10 kW for 2.5 kW between 5 °C and 45 °C has a COP of 4 against a Carnot COP of 7.9537, 50.291 % of the limit; it generates 4.4678 W/K and loses 1.2427 kW of work.

Limitations

  • Two reservoirs at constant temperature; machines working over a temperature glide need the mean temperatures of heat transfer, which lowers the true limit.
  • Steady operation at one operating point; seasonal or part-load figures need the temperatures and rates that go with them.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Test a supplier’s COP or efficiency claim before buying
  • Compare a chiller or heat pump with the best any machine could do
  • Show how much power the irreversibility of a machine costs

Who it is for

  • Mechanical and building services engineers
  • Energy auditors
  • Plant and procurement engineers

What you get

  • Actual efficiency or COP and the Carnot limit
  • Share of the Carnot limit and the verdict
  • Heat at the other reservoir, entropy generated, reversible and lost work

Interpreting the result

  • A claim above 100 % of the Carnot limit is impossible: the figures, the temperatures or the operating point do not belong together.
  • Real vapour-compression machines reach well under the Carnot limit because their heat exchangers need temperature differences; the closer the temperatures, the larger the Carnot COP and the harder it is to approach.

Before relying on the result

  • Ask for the test standard and conditions behind any claimed COP or efficiency.
  • Measure inlet and outlet temperatures of both heat exchangers on site before using real operating temperatures.

References

  • Linder, B., Thermodynamics and Introductory Statistical Mechanics (Wiley-Interscience, 2004), sections 4.1–4.4 and 4.11, printed pp. 32–41 and 48: Carnot efficiency 1 − T1 ÷ T2, the Clausius inequality and entropy change with surroundings. Method reference; no source text, tables or examples are reproduced.
  • Rated COP for air conditioners and heat pumps in Australia comes from tests to the AS/NZS 3823 series; use the rating conditions stated with the figure.