Heat Pump, Chiller or Heat Engine Claim Check (Carnot Limit, Second-Law Efficiency, Running Cost)

Is the COP or efficiency claimed for this heat pump, chiller or heat engine possible between these two temperatures, how close does it come to the Carnot limit, and what does it cost to run each year?

Second-law check of a cyclic machine between a hot and a cold temperature: the Carnot limit for a heat pump (T_h ÷ (T_h − T_c)), a chiller (T_c ÷ (T_h − T_c)) or a heat engine (1 − T_c ÷ T_h), the actual COP or efficiency from the useful output and the input, the second-law efficiency (actual ÷ limit) against your acceptance level, and the yearly input energy and its cost; for a heat pump also the saving against heating with direct electric resistance at the same price.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
MachinechoiceWhat the machine is for: a heat pump delivers heat, a chiller removes heat, an engine turns heat into work.
Hot side temperature°CTemperature at which heat is delivered (heat pump, chiller) or taken in (engine): the water or air leaving the hot side at the rating point.
Cold side temperature°CTemperature at which heat is taken in (heat pump, chiller) or rejected (engine): the source water or outdoor air at the rating point.
Useful output (heat delivered, cooling or work)kWRated or measured useful output at these temperatures: heating capacity, cooling capacity or shaft work.
Input (electrical or shaft power, or heat for an engine)kWRated or measured input at the same conditions: electrical power for a heat pump or chiller, heat (fuel) input for an engine.
Lowest second-law efficiency you accept%The second-law efficiency below which you would question the machine or the claim; set it from your own comparisons.
Running cost
Running hours per year at this outputh/yearEquivalent full-load hours a year at this output.
Price of the input energy (including GST)AUD/kWhWhat one kilowatt-hour of the input energy costs you, including GST for a household (exclude it for a GST-registered business).

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Machine
Illustration: MachineThe options for Machine, with the one currently selected highlighted.Heat pump (heating is the useful output)Chiller or refrigeration (cooling is the us…Heat engine (work is the useful output)Example: Heat pump (heating is the…Machine
What it is
Which job the machine does: a heat pump whose product is heat, a chiller whose product is cooling, or an engine whose product is work.
Units and format
Choose one of 3 options from the list: Heat pump (heating is the useful output); Chiller or refrigeration (cooling is the useful output); Heat engine (work is the useful output).
Example
The form opens with “Heat pump (heating is the useful output)” selected as a worked example. Choose the option that matches your case.
Effect on the result
Selects which Carnot limit applies and how the output is read.
Get it right
A reversible air conditioner is a heat pump in winter and a chiller in summer; check each mode at its own temperatures.
What this means: Hot side temperature
Illustration: Hot side temperatureA thermometer whose level rises with Hot side temperature; the level follows the value you type.T_hExample: 55 °CHot side temperature
What it is
The temperature at the warm end of the machine: where a heat pump or chiller rejects heat, or where an engine receives it.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -200 °C to 2000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 55 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher hot side temperature lowers the heat pump and chiller limits and raises the engine limit.
Get it right
Use the fluid temperature at the rating point, for example the hot water leaving a heat pump.
What this means: Cold side temperature
Illustration: Cold side temperatureA thermometer whose level rises with Cold side temperature; the level follows the value you type.T_cExample: 7 °CCold side temperature
What it is
The temperature at the cold end: where a heat pump or chiller takes heat in, or where an engine rejects it.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -270 °C to 2000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 7 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A warmer cold side shrinks the lift, raising the heat pump and chiller limits and lowering the engine limit.
Get it right
For an air-source unit this is the outdoor air temperature at the rating point; for a chiller the chilled water temperature.
What this means: Useful output (heat delivered, cooling or work)
Illustration: Useful output (heat delivered, cooling or work)A motor driving a shaft; Useful output (heat delivered, cooling or work) is the rate at which it does work, energy per second.Q̇Example: 12 kWUseful output (heat delivered, cooling or wor…
What it is
What the machine delivers that you want: heat to the building for a heat pump, heat removed for a chiller or shaft work for an engine.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 10000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 12 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The actual COP or efficiency, and so the second-law efficiency, rise in proportion.
Get it right
Take output and input from the same test point; data sheets often list several.
What this means: Input (electrical or shaft power, or heat for a…
Illustration: Input (electrical or shaft power, or heat for an engine)A motor driving a shaft; Input (electrical or shaft power, or heat for an engine) is the rate at which it does work, energy per second.ẆExample: 3.5 kWInput (electrical or shaft power, or heat for…
What it is
What the machine consumes to deliver that output: electrical or shaft power for a heat pump or chiller, heat input for an engine.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 10000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 3.5 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The actual COP or efficiency is inversely proportional to the input; it also sets the yearly energy and cost.
Get it right
Include fans and pumps that the rating includes, so the COP matches the rating standard.
What this means: Lowest second-law efficiency you accept
Illustration: Lowest second-law efficiency you acceptA bar of 100 parts with the share marked; Lowest second-law efficiency you accept is that share out of 100. The bar follows the value you type.0 %100 %η_minExample: 30%Lowest second-law efficiency you accept
What it is
The share of the Carnot limit below which you would treat the machine or claim as poor, your own acceptance level for the comparison.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 30% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A second-law efficiency below this value turns the verdict to a warning.
Get it right
Set it from machines you have measured or from other quotations at the same temperatures.

Running cost

What this means: Running hours per year at this output
Illustration: Running hours per year at this outputA timeline from a start mark to an end mark; Running hours per year at this output is the time between them.startendtExample: 2000 h/yearRunning hours per year at this output
What it is
The equivalent number of hours a year the machine runs at the output entered, used for the yearly energy and cost.
Units and format
Enter a number in h/year: h/year. The form accepts 0 h/year to 8784 h/year. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2000 h/year as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Yearly energy, cost and saving scale in direct proportion.
Get it right
For part-load running, divide the yearly output energy by the rated output to get equivalent full-load hours.
What this means: Price of the input energy (including GST)
Illustration: Price of the input energy (including GST)A stack of coins and a note representing the money amount Price of the input energy (including GST).cExample: 0.3 AUD/kWhPrice of the input energy (including GST)
What it is
What one kilowatt-hour of the input energy costs you, used for the yearly running cost and the saving over resistance heating.
Units and format
Enter a number in AUD/kWh: Australian dollars per kilowatt-hour. The form accepts 0 AUD/kWh to 100 AUD/kWh. Required: the tool does not calculate until every input is valid.
Example
The form opens with 0.3 AUD/kWh as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Cost and saving scale in direct proportion.
Get it right
A household compares prices including GST; a GST-registered business compares them ex GST.

Method and formulas

  1. Carnot efficiency of a reversible engine between T_h and T_c: η = 1 − T_c ÷ T_h, in kelvin (Greiner eq. 2.56); reversed, the same cycle is the best possible heat pump, COP_h = T_h ÷ (T_h − T_c), or chiller, COP_c = T_c ÷ (T_h − T_c) (Greiner eqs 2.63–2.65).
  2. Actual COP or efficiency = useful output ÷ input; second-law efficiency = actual ÷ Carnot limit. Above 100 % the claim breaks the second law as stated.
  3. Yearly input energy = input × hours; cost = energy × price; heat pump saving = output × hours × price − input cost (direct resistance heating needs one kilowatt-hour per kilowatt-hour of heat).
  4. Example: actual 3.4286 against a Carnot limit of 6.8365, a second-law efficiency of 50.151 %; 7,000 kWh a year costs A$2,100.

Limitations

  • The Carnot limit is the absolute ceiling for the temperatures entered; real machines also lose to the temperature differences across their heat exchangers, so use the source and sink temperatures at the rating point.
  • One operating point: seasonal performance depends on how the temperatures and load vary through the year.
  • Ratings to compare must be at the same conditions; heat pump and air-conditioner ratings in Australia follow the AS/NZS 3823 series of test conditions.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Test a supplier’s COP or efficiency claim against what physics allows
  • Compare heat pumps or chillers on how close they come to the limit
  • Estimate running cost and the saving of a heat pump over resistance heating

Who it is for

  • Mechanical and building services engineers
  • Energy and facilities managers
  • Buyers comparing quotations

What you get

  • Actual COP or efficiency and the Carnot limit
  • Second-law efficiency against your acceptance level
  • Yearly input energy and cost (and, for a heat pump, the saving over direct electric heating)

Interpreting the result

  • Real vapour-compression machines fall well short of the Carnot limit because of heat-exchanger temperature differences and compressor losses; a claim close to the limit deserves its test conditions checked, and one above 100 % is impossible as stated.
  • The limit falls as the temperature lift grows, so lowering the delivery temperature or raising the source temperature improves the COP more than most equipment choices.

References

  • Greiner W., Neise L. and Stöcker H., Thermodynamics and Statistical Mechanics (Springer-Verlag, New York, 1995), pp. 52–58: thermodynamic engines, the Carnot efficiency (eq. 2.56) and heating with a heat pump against electricity (Exercise 2.7, eqs 2.63–2.65). Method reference; no text, tables or worked examples are reproduced.
  • AS/NZS 3823 series, Performance of electrical appliances — Air conditioners and heat pumps: rating and test conditions; requirements are not reproduced here.

Learn the Concepts Behind This Tool

These KEVOS® Library readings explain the method this tool uses, with worked examples.

KEVOS® tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.