Adiabatic Mixing of Two Air Streams (Mixed Temperature, Humidity, Dew Point, Fog Risk)

When outdoor and return air (or any two moist-air streams) mix without heat transfer, what temperature, humidity ratio, relative humidity and dew point does the mixed air have, and does the mixture stay clear of fog?

Adiabatic mixing of two moist-air streams, such as outdoor and return air in an air-handling unit: each stream’s humidity ratio, enthalpy and dry-air flow, the mixed temperature, humidity ratio, relative humidity and dew point, the outdoor share by mass, and a check that the mixture stays clear of fog.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Total (barometric) pressurekPaBarometric pressure at the site: 101.325 kPa at sea level.
Stream 1 (for example outdoor air)
Stream 1 dry-bulb temperature°CDry-bulb temperature of the first stream, often outdoor air at the design condition.
Stream 1 relative humidity%Relative humidity of the first stream.
Stream 1 volume flowm³/sVolume flow of the first stream at its own temperature, from the damper or fan schedule.
Stream 2 (for example return air)
Stream 2 dry-bulb temperature°CDry-bulb temperature of the second stream, often return air from the space.
Stream 2 relative humidity%Relative humidity of the second stream.
Stream 2 volume flowm³/sVolume flow of the second stream at its own temperature.
Limit
Highest acceptable mixed relative humidity%Highest mixed relative humidity you accept before fogging, wet filters or condensation become a risk.

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Total (barometric) pressure
Illustration: Total (barometric) pressureA pressure gauge whose needle moves with Total (barometric) pressure; the needle follows the value you type.PExample: 101.325 kPaTotal (barometric) pressure
What it is
The total pressure of the moist air, the barometric pressure at the site, used in the humidity ratios and specific volumes.
Units and format
Enter a number in kPa: kilopascals. The form accepts 50 kPa to 110 kPa. Required: the tool does not calculate until every input is valid.
Example
The form opens with 101.325 kPa as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Changes the humidity ratios and mass flows slightly.
Get it right
Use about 101.325 kPa at sea level and the local value at altitude.

Stream 1 (for example outdoor air)

What this means: Stream 1 dry-bulb temperature
Illustration: Stream 1 dry-bulb temperatureA thermometer whose level rises with Stream 1 dry-bulb temperature; the level follows the value you type.T₁Example: 5 °CStream 1 dry-bulb temperature
What it is
The dry-bulb temperature of the first air stream, often the outdoor air entering through the outdoor-air damper.
Units and format
Enter a number in °C: degrees Celsius. The form accepts 0 °C to 60 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 5 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A colder first stream lowers the mixed temperature and raises the fog risk.
Get it right
Use the design condition you are checking; the tool accepts 0 to 60 °C.
What this means: Stream 1 relative humidity
Illustration: Stream 1 relative humidityA bar of 100 parts with the share marked; Stream 1 relative humidity is that share out of 100. The bar follows the value you type.0 %100 %φ₁Example: 80%Stream 1 relative humidity
What it is
The relative humidity of the first air stream, which with its temperature sets the moisture it brings to the mix.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0.1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 80% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Higher humidity raises the mixed humidity ratio and dew point.
Get it right
Cold outdoor air often has a high relative humidity but little moisture.
What this means: Stream 1 volume flow
Illustration: Stream 1 volume flowA pipe with liquid or gas moving through it; Stream 1 volume flow is the volume that passes per unit of time.V̇₁Example: 0.5 m³/sStream 1 volume flow
What it is
The volume of the first stream flowing each second at its own temperature, which with its specific volume gives its dry-air mass flow.
Units and format
Enter a number in m³/s: m³/s. The form accepts 0 m³/s to 1000 m³/s. Required: the tool does not calculate until every input is valid.
Example
The form opens with 0.5 m³/s as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A larger flow moves the mix towards the first stream’s condition.
Get it right
Enter 0 to see the second stream alone.

Stream 2 (for example return air)

What this means: Stream 2 dry-bulb temperature
Illustration: Stream 2 dry-bulb temperatureA thermometer whose level rises with Stream 2 dry-bulb temperature; the level follows the value you type.T₂Example: 22 °CStream 2 dry-bulb temperature
What it is
The dry-bulb temperature of the second air stream, often the return air from the conditioned space.
Units and format
Enter a number in °C: degrees Celsius. The form accepts 0 °C to 60 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 22 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A warmer second stream raises the mixed temperature.
Get it right
Measure in the return duct before the mixing box.
What this means: Stream 2 relative humidity
Illustration: Stream 2 relative humidityA bar of 100 parts with the share marked; Stream 2 relative humidity is that share out of 100. The bar follows the value you type.0 %100 %φ₂Example: 50%Stream 2 relative humidity
What it is
The relative humidity of the second air stream, which with its temperature sets the moisture it brings to the mix.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0.1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 50% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Higher humidity raises the mixed humidity ratio and dew point.
Get it right
Occupied spaces add moisture, so return air is often wetter than supply air.
What this means: Stream 2 volume flow
Illustration: Stream 2 volume flowA pipe with liquid or gas moving through it; Stream 2 volume flow is the volume that passes per unit of time.V̇₂Example: 1.5 m³/sStream 2 volume flow
What it is
The volume of the second stream flowing each second at its own temperature, which with its specific volume gives its dry-air mass flow.
Units and format
Enter a number in m³/s: m³/s. The form accepts 0 m³/s to 1000 m³/s. Required: the tool does not calculate until every input is valid.
Example
The form opens with 1.5 m³/s as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A larger flow moves the mix towards the second stream’s condition.
Get it right
Supply flow minus outdoor flow gives the return flow when the system balances.

Limit

What this means: Highest acceptable mixed relative humidity
Illustration: Highest acceptable mixed relative humidityA bar of 100 parts with the share marked; Highest acceptable mixed relative humidity is that share out of 100. The bar follows the value you type.0 %100 %φ_maxExample: 90%Highest acceptable mixed relative humidity
What it is
The highest relative humidity of the mixed air you accept before filters, coils or ducts risk getting wet.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 1% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 90% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Only moves the line between clear and near-saturation results.
Get it right
Allow a margin below 100 % for incomplete mixing and sensor error.

Method and formulas

  1. Each stream: p_v = φ p_sat(T) (Hyland–Wexler), ω = 0.622 p_v ÷ (P − p_v), h = 1.005 T + ω (2,500.9 + 1.82 T), v = 0.287 (T + 273.15) ÷ (P − p_v) and ṁ_a = V̇ ÷ v.
  2. Mixed state: ω₃ and h₃ are averages weighted by dry-air mass flow (mass and energy balances).
  3. Mixed temperature T₃ = (h₃ − 2,500.9 ω₃) ÷ (1.005 + 1.82 ω₃); vapour pressure p_v3 = ω₃ P ÷ (0.622 + ω₃); relative humidity = p_v3 ÷ p_sat(T₃).
  4. Example: 0.5 m³/s at 5 °C and 80 % mixed with 1.5 m³/s at 22 °C and 50 % gives 17.56 °C at 57.7 % (dew point 9.14 °C), clear of fog.

Limitations

  • Perfect, adiabatic mixing; real mixing boxes stratify, so coils and filters can see colder or wetter air than the average.
  • Air temperatures from 0 to 60 °C; relative humidity is taken over liquid water.
  • When the result shows fog, the true mixed state is saturated with some water condensed; the reported state is the unrealisable straight-line mix.
  • Example values are illustrations. Replace them with values for your actual system.

Typical uses

  • Find the mixed-air condition entering a coil from outdoor and return air
  • Check for fog or frosting risk when cold, humid outdoor air meets warm return air
  • Set minimum outdoor air or economiser limits

Who it is for

  • Mechanical services designers
  • HVAC technicians and commissioning engineers
  • Facility engineers

What you get

  • Mixed temperature, relative humidity, dew point, humidity ratio and enthalpy
  • Dry-air mass flows and the first stream’s share
  • Fog and near-saturation check

Interpreting the result

  • On a psychrometric chart the mixed state lies on the straight line between the two streams, closer to the larger one.
  • Fog appears when that line crosses the saturation curve, most often with very cold, humid outdoor air.

Before relying on the result

  • Measure the mixed-air temperature at several points across the coil face to check for stratification.

References

  • Çengel Y. A. and Boles M. A., Thermodynamics: An Engineering Approach, 5th edition (McGraw-Hill, 2006), chapter 14 (sections 14-2 and 14-7: humidity and adiabatic mixing of airstreams). Method reference; no tables, figures or examples are reproduced.
  • ASHRAE Handbook—Fundamentals (SI), chapter 1 Psychrometrics: Hyland–Wexler saturation pressure.