KEVOS® MAKEOS · Hydraulics

Tank Heating or Cooling Coil Plan (Area, Tube Length, Turns, Pressure Drop)

How many turns of tube does my tank heating or cooling coil need for the duty, how long is the tube, and what pressure drop will the water see through it?

Plan for a helical tube coil in a tank: heat-transfer area needed for the duty from the overall coefficient and mean temperature difference, the tube length and turns that give it, the developed length of the coil you choose with its straight ends (as the helix length tool), the area it provides, and the velocity, friction factor and pressure drop of the fluid through the tube (as the pipe friction tool), checked against the duty and your pressure-drop limit.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Heat dutykWHeat to transfer.
Overall heat-transfer coefficientW/(m²·K)Overall coefficient for the coil, tube and fluids (from your heat-transfer data).
Mean temperature differenceKLog-mean (or mean) temperature difference between the fluid in the tube and the tank.
Coil
Mean coil diametermmMean diameter of the coil.
Coil pitchmmAxial pitch of the coil.
TurnsturnsNumber of turns you plan.
Straight ends (total)mmTotal length of the straight inlet and outlet legs.
Tube outside diametermmOutside diameter of the tube.
Tube wallmmWall thickness of the tube.
Fluid in the tube
FlowL/minFlow of the heating or cooling fluid through the tube.
Kinematic viscositycStKinematic viscosity of that fluid.
Densitykg/m³Density of that fluid.
Tube roughnessmmRoughness of the tube bore.
Sum of fitting loss coefficientsLoss coefficients for the entry, exit and fittings.
Largest pressure dropbarLargest pressure drop you accept across the coil.

Method and formulas

  1. Area needed = Q ÷ (U ΔT_m); tube length needed = area ÷ (π × tube OD).
  2. Developed length = turns × √[(π D_c)² + p²] + ends (as the helix length tool); area provided = π × OD × length.
  3. Pressure drop = (f L ÷ d + ΣK) ρ v² ÷ 2 with the Colebrook friction factor for the tube bore (as the pipe friction tool).
  4. Example: 20 kW needs 1 m², about 12.961 turns; 14 turns give 1.077 m² of 13.713 m tube with 0.085323 bar drop.

Limitations

  • Straight-tube friction factor; coil curvature raises the pressure drop somewhat.
  • Overall coefficient must allow for fouling and the tank side agitation.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Size a heating or cooling coil for a tank or bath
  • Check an existing coil for a new duty
  • Find the pressure drop through a coil

Who it is for

  • Plant engineers
  • Process engineers
  • Maintenance engineers

What you get

  • Area and tube length needed, turns needed
  • Developed length and area provided
  • Velocity and pressure drop

Interpreting the result

  • If the drop is too high, split the coil into parallel circuits rather than shortening it.

References

  • Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 2060–2062, 3024–3027, 371–378. Topic reference; no source tables or recommended settings are reproduced.

WORKOS tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.

Open the Tank Heating or Cooling Coil Plan (Area, Tube Length, Turns, Pressure Drop) calculator