Heat Exchanger Sizing (Duty, Outlet Temperature and Area)

How much heat does this exchanger move, what will the cold stream leave at, and is the installed area enough?

Sizing check of a liquid-to-liquid heat exchanger: duty from the hot stream’s flow, specific heat and temperature drop, the cold stream outlet temperature from the energy balance, the log-mean temperature difference for counterflow or parallel flow (as the heat exchanger LMTD tool), the area needed with your overall coefficient, and checks of the installed area and the closest approach temperature.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Hot stream
Hot flowL/minVolume flow of the hot stream.
Hot densitykg/m³Density of the hot fluid.
Hot specific heatkJ/kg·KSpecific heat of the hot fluid (about 1.9–2.1 for mineral oil).
Hot inlet°CHot stream inlet temperature.
Hot outlet°CHot stream outlet temperature wanted.
Cold stream
Cold flowL/minVolume flow of the cooling stream.
Cold densitykg/m³Density of the cold fluid.
Cold specific heatkJ/kg·KSpecific heat of the cold fluid.
Cold inlet°CCold stream inlet temperature.
Exchanger
Flow arrangementchoiceWhether the streams run in opposite directions (counterflow) or the same direction.
Overall heat transfer coefficientW/m²·KOverall heat transfer coefficient for the exchanger type and fluids, including fouling (from the maker or your data).
Installed aream²Heat transfer area of the exchanger fitted or offered.
Closest approach temperature allowedKSmallest temperature difference you accept between the streams at either end.

Method and formulas

  1. Duty = ṁ_h c_ph (T_hi − T_ho), ṁ = flow × density.
  2. Cold outlet T_co = T_ci + duty ÷ (ṁ_c c_pc).
  3. LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂) with the end differences for the flow arrangement (as the LMTD tool).
  4. Area needed = duty ÷ (U × LMTD).
  5. Example: cooling 30 L/min from 70 to 50 °C moves 41.8 kW; the water leaves at 35 °C and 3.5161 m² is needed.

Limitations

  • Pure counterflow or parallel flow; shell-and-tube with several passes needs an LMTD correction factor.
  • Constant specific heats and no phase change.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Size an oil or coolant cooler for a machine
  • Find the water outlet temperature of a cooler
  • Check whether an existing exchanger has enough area

Who it is for

  • Plant engineers
  • Hydraulic engineers
  • Maintenance engineers

What you get

  • Duty and cold outlet temperature
  • LMTD and area needed
  • Area and approach checks

Interpreting the result

  • Counterflow needs less area for the same duty and lets the cold outlet exceed the hot outlet.

References

  • Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 371–378. Topic reference; no source tables or recommended settings are reproduced.