← ArticlesBuilding Physics: Heat, Light, Sound and Sustainability: Open-Cycle CoolingEngineering · Civil & StructuralLesson 2/4← PrevNext →
GuidePublished 14 Aug 202623 min readBy Kevin JoginCivil EngineeringBuilding EngineeringBuilding Physics: HeatLight

Engineering · Civil Engineering · Building Engineering

Building Physics: Heat, Light, Sound and Sustainability: Open-Cycle Cooling

Engineering handbook for building physics: heat, light, sound and sustainability, covering open-cycle cooling: the overlooked alternative, light — the luminous...

Executive summary

This handbook section converts the supplied engineering material into a practical, source-controlled reference. It concentrates on the following learning outcomes.

Open-Cycle Cooling: The Overlooked Alternative
LIGHT — The Luminous Environment
Designing for How You Actually See
The Physics of Light — What Your Eyes Evolved to Detect
Colour: The Quality of Light
Surface Colours: The Munsell System

Open-Cycle Cooling: The Overlooked Alternative

In hot-dry climates, evaporative cooling can replace or supplement air conditioning:

  • Direct evaporative cooling: Air passes through a wet pad, giving up heat to evaporate water. The air is cooled but humidified.
  • Indirect evaporative cooling: A secondary air stream is evaporatively cooled and used to cool a heat exchanger, which then cools the primary air supply without adding moisture.

When outdoor air is 42°C and 10% RH, a direct evaporative cooler can deliver air at 24°C — with zero compressor energy. The only cost is the fan and water.



LIGHT — The Luminous Environment


Designing for How You Actually See



The Physics of Light — What Your Eyes Evolved to Detect

the practitioner was a lighting consultant called in to fix a brand-new office tower where workers complained of headaches, fatigue, and an inability to concentrate. The lighting met every code requirement. The problem wasn't the quantity of light. It was everything else about it.

Light is electromagnetic radiation in the narrow wavelength band from 380 nm (violet) to 780 nm (red) — a tiny sliver of the full electromagnetic spectrum that happens to activate our visual system.


Colour: The Quality of Light

The colour of light is determined by its spectral composition — which wavelengths are present and in what proportions:

Colour Wavelength Band (nm)
Red 780–660
Orange 660–610
Yellow 610–570
Green 550–510
Blue 480–440
Violet 440–380

Colour temperature rates the apparent colour of a light source against the colour of a heated black body:

Colour Temperature Appearance Example
~1,800 K Warm orange Candle flame
~2,700 K Warm white Incandescent lamp
~3,000 K Warm white Halogen lamp
~4,000 K Neutral white Cool fluorescent
~5,500 K Daylight white Direct sunlight
~6,500 K Cool white Overcast sky
~24,000 K Blue Blue sky

The counter-intuitive naming: "Warm" colours have low colour temperatures, "cool" colours have high colour temperatures.


Surface Colours: The Munsell System

The Munsell system describes any surface colour with three attributes:

  • Hue: The colour name (red, yellow, green, blue, purple, and intermediates)
  • Value (V): Lightness, 0 (black) to 10 (white). Converts to reflectance: ρ = V × (V−1) / 100
  • Chroma: Saturation or intensity of the colour

Photometry: Measuring Light for Human Vision

Four quantities define the lighting in any space:

Quantity Symbol Unit What It Measures
Luminous intensity I candela (cd) Strength of a light source in a direction
Luminous flux Φ lumen (lm) Total light output of a source
Illuminance E lux (lx) = lm/m² Light falling on a surface
Luminance L cd/m² Brightness of a surface as seen by the eye

Key relationships:

E = I / d² (Inverse square law — illuminance drops with the square of distance)

E = E_n × cos θ (Cosine law — illuminance drops with angle of incidence)

Some reference illuminance values:

Condition Illuminance (lux)
Bright sunny day, outdoors 80,000
Overcast day, outdoors 5,000
Well-lit office desk 300–500
Average general room lighting 100
Full moonlit night 0.1

Luminous efficacy — how efficiently a source converts power into visible light — measured in lm/W:

Source Efficacy (lm/W)
Candle ~0.3
Incandescent (100W) ~17
Halogen ~20
Compact fluorescent ~60
Fluorescent tube ~80–100
LED ~100–200
Maximum theoretical 683 (at 555 nm)


Vision — Designing for the Biological Eye

the practitioner's investigation revealed the real problem: the office had uniform 500 lux across every surface, with fluorescent tubes of 6,500 K colour temperature — cold, flat, and relentless. The space had the visual character of a hospital laboratory. No contrast, no warmth, no visual hierarchy. The workers' eyes were stressed not by too little light, but by light that contradicted every biological expectation.


How the Eye Works

The retina contains two types of receptors:

  • Cones (~6.5 million): Concentrated in the fovea, sensitive to both quantity and colour of light, operate only in good lighting (photopic vision)
  • Rods (~125 million): Spread across the retina, more sensitive but see only brightness, no colour (scotopic vision)

Adaptation:

  • Pupil response: Nearly instantaneous, adjusting to average luminance
  • Retinal adaptation to darkness: Up to 30 minutes (visual purple production)
  • Retinal adaptation to brightness: About 3 minutes (visual purple removal)

This is why emerging from a dark cinema into daylight is uncomfortable for seconds, but entering a dark room takes minutes to adjust. Design implication: Transition zones between bright and dim spaces should provide gradual luminance changes.


Visual Performance Factors

Contrast sensitivity — In full daylight, you can distinguish a 1% luminance difference. In poor lighting, surfaces with 10% difference may appear identical. Contrast is defined as:

C = (L₁ − L₂) / L₂

Visual acuity — Sharpness of vision improves with illuminance, following a diminishing-returns curve. A small increase at low light levels produces dramatic improvement; the same increase at high levels produces barely any difference.

This means the first 200 lux on a desk produces far more visual benefit than increasing from 500 to 700 lux. Over-lighting is wasteful twice — in energy and in effectiveness.


Glare: The Enemy of Good Lighting

Discomfort glare reduces visual efficiency and causes annoyance. Disability glare actually impairs vision.

Causes:

  • Luminance ratio (L_max / L_min) within the field of vision greater than about 10–15
  • Direct view of bright light sources
  • Reflections of light sources in glossy surfaces ("veiling reflections")
  • Bright windows behind a task (computer screens are the worst offenders)

Contrast grading is the primary defense:

  • Visual task luminance = 100%
  • Immediate surroundings ≥ 50%
  • Rest of the visual field ≥ 20%


Daylight Design — Harnessing the Best Light Source in the Universe

the practitioner's recommendation was radical: reduce the electric lighting by 60% and redesign the window layout. "The sun delivers 100,000 lux for free," he told the building owner. "Your building is rejecting 99% of it and then spending a fortune to replace it with inferior artificial light."


Sky Conditions

The available daylight depends on sky type:

  • CIE standard overcast sky: Luminance is three times brighter at zenith than at the horizon. The illuminance on the ground depends on the sun's altitude behind the clouds: E ≈ 200 × ALT (lux)
  • Clear sky: Up to 100,000 lux direct sunlight, 40,000–50,000 lux diffuse
  • Intermediate sky: E ≈ 500 × ALT (lux)

The Daylight Factor

The Daylight Factor (DF) is the ratio of indoor illuminance to outdoor horizontal illuminance under an overcast sky, expressed as a percentage:

DF = (E_indoor / E_outdoor) × 100%

It has three components:

  • Sky Component (SC): Direct light from the visible sky
  • Externally Reflected Component (ERC): Light reflected from external surfaces
  • Internally Reflected Component (IRC): Light reflected from internal surfaces

Design targets:

Space Minimum DF Average DF
Living rooms 0.5% 1.5%
Offices 2% 5%
Classrooms 2% 5%
Art studios 4–6% 10%+

Planning for Daylight: Rules of Thumb

  • Room depth should not exceed 2× the window head height for adequate daylight penetration
  • Window area of 20–25% of floor area typically provides adequate daylight in side-lit rooms
  • Light shelves can redirect daylight deeper into spaces
  • Roof lights are 3× more effective than side windows for the same area (they see more sky)
  • Toplighting should provide 2–5% of floor area for workspaces


Electric Lighting — The Artificial Sun


Lamp Types and Their Characteristics

Lamp Type Efficacy (lm/W) Colour Temp (K) Colour Rendering (CRI) Life (hours)
Incandescent 10–17 2,700 100 1,000
Halogen 15–25 3,000 100 2,000–4,000
Compact fluorescent 50–70 2,700–6,500 80–90 8,000–15,000
Fluorescent tube (T5) 80–104 3,000–6,500 80–95 15,000–30,000
LED 80–200+ 2,700–6,500 80–98 25,000–50,000+
High-pressure sodium 80–130 2,000 25 12,000–24,000

The relationship between colour temperature and illuminance level is crucial:

At high illuminances (500+ lux), people prefer higher colour temperatures (4,000–5,000 K — "daylight white"). At low illuminances (< 200 lux), lower colour temperatures (2,700–3,000 K — "warm white") are preferred. Getting this relationship wrong creates spaces that feel clinical, sterile, or uncomfortable, even though the illuminance level is "correct."

This was exactly the practitioner's diagnosis. The office had cold light (6,500 K) at moderate levels (500 lux) — a combination that falls in the "disliked" zone on the Kruithof curve.


Lighting Design Method: The Lumen Method

The total luminous flux required to achieve a target illuminance:

Φ = (E × A) / (UF × MF)

Where:

  • E = target illuminance (lux)
  • A = room area (m²)
  • UF = utilization factor (fraction of lamp output reaching the work plane — depends on room proportions, surface reflectances, and luminaire type)
  • MF = maintenance factor (accounts for lamp ageing and dirt accumulation — typically 0.6–0.8)

Number of luminaires = Φ / (flux per luminaire)



SOUND — The Sonic Environment


The Invisible Architecture of What You Hear



The Physics of Sound — Vibrations That Shape Experience

the practitioner was an acoustic consultant hired to save a new concert hall that had been called "acoustically dead" by every critic who heard it. The architect had created a visually stunning space. But sound doesn't care about aesthetics — it obeys physics.

Sound is mechanical vibration transmitted through a medium. In buildings, we deal with airborne sound (vibrations in air) and structureborne sound (vibrations in the building fabric).


The Fundamental Properties

Property Symbol Unit Meaning
Frequency f Hz (hertz) Vibrations per second — perceived as pitch
Wavelength λ m Distance between wave peaks
Velocity v m/s Speed of propagation (≈340 m/s in air)
Sound power P W Total acoustic energy output
Sound pressure p Pa Pressure variation in the medium
Sound intensity I W/m² Power per unit area

The fundamental relationship: v = f × λ

At 340 m/s: a 100 Hz bass note has a wavelength of 3.4 m; a 4,000 Hz treble note has a wavelength of 0.085 m (85 mm). This wavelength difference is why bass sounds bend around obstacles (diffraction) while treble sounds cast sharp acoustic shadows.


Sound Power: A Sense of Scale

Source Sound Power
Jet airliner 10,000 W (10⁴ W)
Pneumatic riveter 1 W
Large symphony orchestra 0.01 W (10⁻² W)
Conversational speech 0.00001 W (10⁻⁵ W)

A full symphony orchestra produces just one-hundredth of a watt — less than a dying flashlight bulb. The human ear is extraordinarily sensitive.


The Decibel Scale: Compressing the Incomprehensible

The ear responds logarithmically to stimulus intensity (Fechner's law). The decibel (dB) scale compresses the enormous range of human hearing:

Sound Intensity Level: L = 10 × log(I / I₀)

Sound Pressure Level: L = 20 × log(p / p₀)

Reference values (threshold of audibility):

  • I₀ = 10⁻¹² W/m²
  • p₀ = 20 × 10⁻⁶ Pa

Critical: Decibels don't add linearly.

Two sources of 90 dB and 80 dB produce:

  • NOT 170 dB
  • But rather 90.4 dB (intensities add, then convert back to dB)

Rule of thumb: Doubling intensity adds 3 dB. Doubling sound pressure adds 6 dB. A 10 dB increase sounds approximately twice as loud.


Frequency Weighting: The A-Weighted Scale

The ear is not equally sensitive to all frequencies — most sensitive around 4,000 Hz, much less sensitive to low frequencies. The A-weighting filter approximates this frequency response. Sound levels measured with A-weighting are reported as dBA — the most commonly used single-figure descriptor of environmental sound.



Hearing — The Human Sound Receiver

The ear is a remarkable transducer:

  • Outer ear (auditory tube): Collects and funnels sound to the eardrum
  • Middle ear (ossicles): Three tiny bones (hammer, anvil, stirrup) amplify vibration 20×
  • Inner ear (cochlea): 25,000 hair cells selectively respond to different frequencies, converting vibration to nerve impulses

The audible range: 20 Hz to 16,000 Hz (reducing with age — a 60-year-old may lose 70 dB sensitivity at 16 kHz, but only 10 dB at 1 kHz).

Hearing damage:

  • Continuous exposure above 85 dBA causes gradual permanent damage
  • Brief exposure above 120 dBA causes pain
  • Above 140 dBA: immediate permanent damage possible

For building designers: The primary concerns are protecting occupants from harmful noise levels and providing acoustic conditions appropriate for the intended activities.



Noise Control — Defending Against Unwanted Sound

the practitioner's first job, years before the concert hall, was soundproofing apartments above a nightclub. "That project taught me," she said, "that noise control is a war, and every gap in your armour is a total defeat."


Noise Criteria

Background noise levels appropriate for different spaces:

Space NC Curve / dBA
Concert hall NC 15–20 / 25–30 dBA
Bedroom at night NC 25–30 / 30–35 dBA
Private office NC 30–35 / 35–40 dBA
Open-plan office NC 35–40 / 40–45 dBA
Restaurant NC 40–45 / 45–50 dBA
Workshop NC 50–60 / 55–65 dBA

Sound Transmission Loss (TL)

When sound hits a wall or partition, some is reflected, some is absorbed, and some is transmitted through. The Transmission Loss (TL) measures how much is stopped:

TL = 10 × log(1/τ) where τ is the transmission coefficient

The Mass Law: For a single-leaf partition, TL increases approximately 6 dB for every doubling of mass per unit area, and approximately 6 dB for every doubling of frequency.

Wall Construction Mass (kg/m²) Approx. STC/Rw
Single plasterboard (13mm) 10 25–28
Double plasterboard (2×13mm) 20 30–33
110mm brick 200 45
220mm brick 400 50
Staggered stud double plasterboard 25 50+
Isolated double-leaf with cavity varies 55–65+

The Weak Link Principle: Sound transmission is governed by the weakest element. A wall with STC 50 that has a gap of 1% of its area drops to effectively STC 30. Doors, windows, service penetrations, and gaps are where noise control succeeds or fails.


Flanking Transmission

Sound doesn't only go through walls — it goes around them:

  • Through the floor slab connecting two rooms
  • Through the ceiling plenum (above a dropped ceiling)
  • Through ductwork connecting spaces
  • Through structural elements that bypass the partition

The lesson: A partition is only as good as the weakest flanking path. You must address every route sound can take between spaces.


Impact Sound

Footsteps, dropped objects, and machinery create vibrations that travel directly through the building structure. Impact sound is controlled by:

  • Soft surface coverings (carpet, resilient flooring) — absorb the initial impact
  • Floating floors — a structural slab with a resilient layer supporting the finish floor
  • Isolated ceilings — hung on resilient hangers below the structural slab


Room Acoustics — Shaping Sound Inside Spaces

Back to the practitioner's concert hall. The problem wasn't noise from outside — it was what happened to sound inside. The room was killing the music.


Reverberation: The Persistence of Sound

When a sound source stops, the sound doesn't disappear instantly — it bounces off surfaces, gradually losing energy with each reflection. Reverberation time (RT₆₀) is the time for sound to decay by 60 dB after the source stops.

RT₆₀ = 0.161 × V / A

(Sabine formula)

Where:

  • V = room volume (m³)
  • A = total sound absorption in the room (m² sabins = Σ surface areas × absorption coefficients)

Ideal reverberation times depend on room use and volume:

Room Type Optimal RT₆₀ (seconds)
Recording studio 0.2–0.4
Speech/lecture room 0.6–0.8
Multi-purpose hall 1.0–1.5
Concert hall (chamber music) 1.4–1.8
Concert hall (symphonic) 1.8–2.2
Cathedral/organ music 2.5–4.0+

the practitioner's concert hall had an RT₆₀ of 0.8 seconds — perfect for a lecture theatre, fatal for symphonic music. The hard surfaces the architect chose for their visual drama were absorbing almost no sound, but the room was too small for the reflections to build up properly. It was the worst combination: not reverberant enough for music, not dry enough for speech.


Absorption Coefficients

The absorption coefficient (α) of a surface measures the fraction of incident sound energy that is not reflected. It varies with frequency:

Material 125 Hz 500 Hz 2000 Hz 4000 Hz
Concrete/brick (unpainted) 0.01 0.02 0.02 0.05
Plaster on masonry 0.01 0.02 0.04 0.04
Timber panelling 0.10 0.10 0.08 0.08
Heavy carpet on underlay 0.10 0.30 0.50 0.60
Acoustic tile (25mm) 0.20 0.70 0.80 0.60
Open window 1.00 1.00 1.00 1.00

Design principle: Use absorptive materials (high α) to reduce reverberation and control noise. Use reflective materials (low α) to project sound and create liveliness. The art is in the balance.


Room Shape and Sound Distribution

The geometry of a room profoundly affects what listeners hear:

  • Concave surfaces (domed ceilings, curved walls) focus sound, creating "hot spots" and "dead zones" — generally to be avoided
  • Convex surfaces scatter sound, promoting even distribution — generally desirable
  • Parallel walls create flutter echoes — can be broken by angling one wall 5–8°
  • Large flat rear walls cause delayed reflections that interfere with the direct sound — should be treated with absorption


RESOURCES — Energy, Water, and the Survival Question


The Mathematics of Whether Civilization Continues



Energy — The Currency That Runs Everything

Twelve years into her career, the practitioner stood at a conference podium. "I spent the first years learning to design buildings that work," she told the audience. "Now I understand something harder: the energy that flows through every building I design is the same energy that's changing our climate. The building isn't just a thermal filter — it's an ethical statement."


Energy: One Unit to Rule Them All

Energy is the potential for doing work, measured in joules (J). Power is energy flow rate, measured in watts (W = J/s).

The practical energy unit: kilowatt-hour (kWh)

1 kWh = 3,600,000 J = 3.6 MJ

This is what appears on electricity bills worldwide. It's the energy consumed by a 1,000 W appliance running for one hour.

Conversion from legacy units:

Unit Equivalent
1 barrel of oil ~1,667 kWh
1 tonne of oil equivalent (TOE) ~11,630 kWh
1 tonne of coal equivalent (TCE) ~8,056 kWh
1 British thermal unit (Btu) ~0.293 Wh
1 kilocalorie (kcal) ~1.16 Wh

The Power of Wind: A Physics Lesson

Wind power is proportional to velocity cubed:

P_wind = ½ × A × ρ × v³

Where A is the swept area, ρ is air density (≈1.2 kg/m³), and v is wind speed.

This means: doubling wind speed increases power 8×. A location with 8 m/s average wind has 8 times the wind energy of a 4 m/s location — not double.


The Energy Crisis: What the Numbers Say

The world consumes oil at the rate of roughly 71 million barrels per day. Total estimated reserves are approximately 960 billion barrels. The simple division (the "static index") gives about 37 years.

But it won't happen that way. As supplies diminish, prices rise, consumption falls, and alternatives become competitive. The real danger isn't running out — it's the climate damage from burning what we have.


Electricity: Humanity's Most Versatile Energy Form

Electricity generation from fossil fuels involves a triple conversion: chemical → thermal → mechanical → electrical. The overall efficiency is typically 30–35% — meaning 65–70% of the fuel's energy is wasted as heat.

Conversion efficiencies of various systems:

Process Device Efficiency
Chemical → Heat Open fireplace 0.30
Chemical → Heat Gas boiler 0.75
Heat → Mechanical Steam turbine 0.20–0.50
Chemical → Mechanical Diesel engine 0.32–0.38
Mechanical → Electrical AC generator 0.97
Electrical → Mechanical AC motor 0.92

Cogeneration (Combined Heat and Power) captures the "waste" heat from electricity generation for useful heating, achieving 70–80% overall efficiency — more than double a conventional power station.



Renewable Energy — The Only Long-Term Answer


Solar Energy: Direct Applications

Solar thermal systems — Low-temperature applications:

System Application Typical Efficiency
Flat-plate collector Domestic hot water 40–60%
Evacuated tube collector Hot water, space heating 50–70%
Solar air heater Space heating, crop drying 30–50%
Swimming pool heater Pool heating 60–80%

Passive vs. Active distinction:

  • Passive system: CoP > 50 (energy delivered / energy consumed by the system itself)
  • Hybrid system: 20 < CoP < 50
  • Active system: CoP < 20

Photovoltaic (PV) systems convert sunlight directly to electricity:

PV Technology Typical Efficiency
Monocrystalline silicon 15–22%
Polycrystalline silicon 13–18%
Thin film (amorphous) 6–13%
Multi-junction (concentrated) 30–45%

Wind Energy

Wind turbines convert kinetic energy to electricity. Key metrics:

  • Capacity factor: Actual output / theoretical maximum (typically 25–40%)
  • Cut-in speed: Minimum wind speed to start generating (typically 3–4 m/s)
  • Rated speed: Wind speed at maximum output (typically 12–15 m/s)
  • Cut-out speed: Maximum safe operating speed (typically 25 m/s)

Large modern turbines can reach 5–15 MW capacity with rotor diameters exceeding 150 m.


Hydroelectric Power

Potential energy of elevated water:

E_p = M × g × h

Where M is mass (kg), g is gravitational acceleration (9.81 m/s²), and h is height difference (m).

1 m³ of water falling 100 m: E = 1000 × 9.81 × 100 = 981,000 J = 981 kJ ≈ 0.27 kWh

If that water flows at 1 m³/s, the power output is 981 kW (before efficiency losses).



Energy Use in Buildings — Where the Waste Lives

Buildings account for approximately 42% of all energy consumption globally. This breaks down into:

  • Heating and cooling: 50–70% of building energy in most climates
  • Lighting: 15–25%
  • Hot water: 10–20%
  • Equipment and appliances: 10–20%

Energy Rating Systems

Buildings worldwide are increasingly rated for energy performance:

Rating Performance
1 Star — POOR Poor management or outdated systems, consuming much unnecessary energy
2 Stars — GOOD Average performance, some efficiency elements in place
3 Stars — VERY GOOD Current best practice, good systems and management
4 Stars — EXCELLENT Exceeds best practice, innovative solutions
5 Stars — EXCEPTIONAL Leadership-level performance, demonstrating what's possible

CO₂ emission conversion factors for building energy:

Energy Source kg CO₂ per kWh
Electricity (average) 0.72
Solid fuel (coal, coke) 0.34
Fuel oil 0.29
Natural gas 0.21


Water, Wastes, and the Full Picture


Water in Buildings

Water consumption in buildings includes:

  • Domestic/sanitary use: Toilets, showers, hand washing
  • Mechanical systems: Cooling towers, boilers
  • Irrigation and maintenance

Water conservation strategies:

  • Low-flow fixtures and dual-flush toilets (can reduce consumption by 30–50%)
  • Rainwater harvesting for non-potable uses
  • Greywater recycling (shower/basin water reused for toilet flushing/irrigation)
  • Waterless urinals

Waste Management in Building Design

Buildings generate approximately 25% of solid wastes and 20% of liquid wastes.

Design for waste reduction:

  • Specify materials with recycled content
  • Design for disassembly (bolted connections rather than adhesive)
  • Minimize off-cuts through modular dimensioning
  • Provide adequate space for waste sorting and recycling
  • Compost organic waste on-site where possible


Sustainability — The Architect's Responsibility

the practitioner's career had taken her from that failed clinic to designing net-zero-energy buildings across three continents. But the final lesson was the hardest.

"Sustainability isn't a technology," she told a graduating class. "It's a commitment. Every building you design is a 50–100 year bet on the future. Make it count."


The Brundtland Definition

"Sustainable development is development that meets the needs of the present without compromising the ability of future generations to meet their own needs."


What Buildings Contribute to the Problem

Impact Category Buildings' Share
Global energy consumption 42%
Atmospheric emissions 40%
Raw materials used 30%
Water usage 25%
Solid wastes 25%
Liquid wastes 20%

Every one of these can be strongly influenced by architects and designers.


Embodied Energy: The Hidden Cost of Materials

The energy used to extract, manufacture, transport, and install building materials is the embodied energy (or Process Energy Requirement, PER):

Category Material Embodied Energy (kWh/kg)
Low (< 1 kWh/kg) Sand, gravel 0.01
Air-dried sawn hardwood 0.14
Concrete 0.2
Stabilised earth 0.19
Clay bricks 0.69
Medium (1–10 kWh/kg) Plasterboard 1.0–1.22
Cement 2.2–5.6
Glass 3.5–6.0
Mild steel 9.44–10
High (> 10 kWh/kg) Plastics in general 10–25
Zinc 14–15
Copper 16–28
Aluminium 47–56

The Operational/Capital energy ratio: In the 1970s, a building used as much energy in operation over 5 years as was embodied in its construction (O/C ratio = 5). Today, improved buildings show ratios of 30–50 — meaning better operations have shifted focus toward reducing embodied energy.


The Four Pillars of Sustainable Design

1. Site:

  • Preserve undisturbed land where possible
  • Use already-disturbed or derelict land
  • Prevent soil erosion
  • Promote higher density to reduce sprawl and transport

2. Energy:

  • Maximize passive strategies first
  • Right-size active systems
  • Use renewable energy sources
  • Target net-zero operational energy

3. Materials:

  • Prefer low-embodied-energy materials
  • Use renewable, plantation-sourced timber
  • Specify recycled content
  • Design for longevity, adaptability, and eventual disassembly

4. Wastes:

  • Minimize construction waste through modular design
  • Design for on-site water recycling
  • Provide for waste sorting in operation
  • Retain stormwater on-site

Building Materials Assessment

A comprehensive evaluation uses 14 criteria grouped across the building lifecycle:

Lifecycle Stage Criteria
Raw Materials Environmental damage in extraction, extent relative to output, abundance/renewability, recycled content
Manufacture Solid/liquid wastes, air pollution, embodied energy
Construction Transport energy, assembly energy, on-site waste
In Use Maintenance requirements, toxic emissions during lifecycle
Demolition Demolition energy/effects, recyclability


Your Next Steps

If you're a beginner: Start with one thing — master the U-value calculation. Understand how heat flows through one wall. Then expand to the whole building.

If you're a practitioner: Audit your last project. How much of the heating/cooling load was caused by design decisions you could have changed? What would you do differently?

If you're making decisions about buildings: Ask your architect one question: "What is the building's annual energy consumption per square metre, and how does that compare to best practice?"

If they can't answer, you need a different architect.



Quick Reference: Essential Formulas

Formula Application Variables
Q = A × U × ΔT Heat flow through building elements Q: heat flow (W), A: area (m²), U: transmittance (W/m²K), ΔT: temperature difference (K)
R = b / λ Thermal resistance of a layer R: resistance (m²K/W), b: thickness (m), λ: conductivity (W/mK)
U = 1 / R_total Transmittance from total resistance Sum all R values (surfaces + layers)
Q_s = A × G × α Solar heat gain on opaque surface G: irradiance (W/m²), α: absorptance
Q_s = A × G × θ Solar heat gain through glass θ: solar gain factor
T_n = 17.6 + 0.31 × T_o Thermal neutrality temperature T_o: annual mean outdoor temp (°C)
HDD = Σ(T_b − T_o) Heating degree-days T_b: balance point temp
E = I / d² Illuminance from point source I: intensity (cd), d: distance (m)
DF = E_in / E_out × 100 Daylight factor Ratio of indoor to outdoor illuminance
L = 10 × log(I/I₀) Sound intensity level I₀ = 10⁻¹² W/m²
L = 20 × log(p/p₀) Sound pressure level p₀ = 20 × 10⁻⁶ Pa
RT₆₀ = 0.161 × V / A Reverberation time V: volume (m³), A: total absorption (m² sabins)
P_wind = ½ × A × ρ × v³ Wind power ρ: air density (~1.2 kg/m³), v: wind speed (m/s)
CoP = Output / Input Heat pump performance Higher is better — 3 to 5 for good heat pumps


Complete Glossary of Key Terms

Term Definition Unit
Absorptance (α) Fraction of incident radiation absorbed by a surface — (0–1)
Admittance (Y) Thermal property relating to cyclic heat flow at a surface W/m²K
Conductance (C) Heat flow density per degree through a body W/m²K
Conductivity (λ) Heat flow density per degree per unit thickness of a material W/mK
Decrement factor (μ) Ratio of indoor to outdoor temperature swing through a wall — (0–1)
Degree-days (DD) Cumulative temperature difference below/above a base Kd
Emittance (ε) Ability to emit radiation relative to a black body — (0–1)
Illuminance (E) Light falling on a surface lux (lm/m²)
Luminance (L) Brightness of a surface as perceived by the eye cd/m²
Reflectance (ρ) Fraction of incident radiation reflected — (0–1)
Resistance (R) Opposition to heat flow m²K/W
Reverberation time (RT₆₀) Time for sound to decay 60 dB seconds
Sol-air temperature Effective outdoor temperature including solar radiation effects °C
Sound level (L) Logarithmic measure of sound intensity or pressure dB
Thermal bridge Area where insulation is compromised, allowing excess heat flow
Time lag (φ) Delay between outdoor temperature peak and indoor appearance hours
Transmittance (U) Heat flow density per degree, air-to-air W/m²K
Vapour pressure (pv) Partial pressure of water vapour in air Pa

The building is not just a shelter. It is a selective filter — excluding the unwanted, admitting the desirable. Master heat, light, sound, and energy, and you don't just design buildings. You design the conditions for human life.

What question about your building's performance will you investigate first? Share in the comments below — or better yet, pick up a thermometer, a light meter, or a sound level app and start measuring. The physics is already happening. Your job is to make it work for the people inside.


Based on the principles presented in "Introduction to Architectural Science: The Basis of Sustainable Design" by Steven V. Szokolay — the foundational text bridging building physics with sustainable practice.

Engineering use and verification

Coordinate structure, envelope, water, fire, electrical and mechanical services as one building system. Establish climate, use, occupancy, loads, resilience, maintainability and commissioning criteria before detailed selection. Check interfaces and access at each design stage, and verify calculations against the applicable jurisdiction, project brief and current standards. Values from the source are educational unless adopted through the project's controlled design process.

  • Confirm scope, assumptions, interfaces and required outcome.
  • Use one controlled unit system and show every conversion.
  • Identify current project, customer and regulatory requirements.
  • Separate source examples from mandatory acceptance criteria.
  • Check calculations, tables and selections by an independent method.
  • Verify safety, maintainability and credible failure modes.
  • Record evidence, revisions, approvals and unresolved limitations.
  • Validate the result under representative operating conditions.

Continue learning

Building Physics: Heat, Light, Sound and Sustainability: The Physics That Governs Every Building on EarthGuide · Civil & StructuralNEXT LESSON →Psychrometrics for HVAC Design and Troubleshooting: What Is Psychrometrics, and Why Should You Care?Guide · Civil & StructuralPsychrometrics for HVAC Design and Troubleshooting: the practitioner's ResolutionGuide · Civil & StructuralEngineering History: Materials, Structures and Water SystemsGuide · Civil & Structural